Fire Extinguishers at Home and Work: Choose and Check

Which extinguisher for which fire, where to mount it and how often to service it: Turkish rules call for a yearly check and a refill and test every four years.

Titan SavunmaOriginal Article: Updated: Approximately 7 min read
A production room with stainless steel equipment and a fire extinguisher on the wall.
In This Article

Under Turkey's Regulation on Fire Protection of Buildings, fire extinguishers get an on-site general inspection once a year, and at the end of the fourth year the extinguishing agent is replaced and the cylinder is hydrostatically tested. Periodic inspection and maintenance follow TS ISO 11602-2 and must be carried out by firms holding a filling and service competence certificate. An extinguisher that has been used must be refilled, whatever its date.

This article is general information, not legal advice. Confirm the number and location requirements for your building class against the current regulation and with the local fire brigade.

This piece is about choosing the right extinguisher, placing it well and keeping it ready, rather than about fighting a fire. For security teams' duties during a fire, see our article on security duties in fire and emergency coordination.

Fire classes and the right extinguisher

The choice depends on what could burn. Article 99 of the regulation names the preferred type for each class:

  • Class A (solids such as paper, wood, fabric): multi-purpose dry powder (ABC) or water.
  • Class B (flammable liquids such as petrol, thinner, paint): dry powder, carbon dioxide (CO2) or foam.
  • Class C (flammable gases such as LPG and natural gas): dry powder or CO2.
  • Class D (flammable metals): dry metal powder.
  • Cooking oils and fats (Class F in Europe, Class K in the US): only an extinguisher rated and labelled for Class F (or K).
  • Live electrical equipment: an agent that does not conduct electricity, such as CO2 or a suitable powder.

One source of confusion: in Europe and Turkey, Class C means flammable gases, while in the United States Class C means energised electrical equipment. Check which system a guide uses before following it. For hospitals, care homes and nurseries, the Turkish regulation prefers water or clean-gas extinguishers.

What the regulation requires: numbers, placement, standards

The main rules in Article 99 of the Regulation on Fire Protection of Buildings are:

  • Number: one 6 kg dry powder extinguisher (or gas equivalent) for every 500 m² of construction area in low-hazard buildings, and for every 250 m² in medium- and high-hazard buildings.
  • Wheeled units: car parks, storage areas and plant rooms must also have a wheeled extinguisher.
  • Placement: near exits, evenly distributed, clearly marked and easy to reach, with a maximum travel distance of 25 metres. Not behind doors, inside closed cupboards (fire cabinets excepted), in deep recesses, or on or beside heaters.
  • Height: units weighing 4 to 12 kg are hung on an easily released wall bracket so that they sit no higher than about 90 cm from the floor.
  • Standards: portable units must be certified to TS 862-EN 3 and wheeled units to TS EN 1866.
  • Boiler rooms: Article 54 separately requires at least one 6 kg multi-purpose dry powder extinguisher in boiler rooms.

The local fire brigade may also be consulted on type, number and location. Our encyclopedia entry on the fire protection regulation for buildings gives the wider context.

Servicing and refilling

The short answer to “how often” sits in the same article: inspection and maintenance follow TS ISO 11602-2, there is a general on-site inspection once a year, and at the end of the fourth year the agent is renewed and a hydrostatic test carried out. Service firms must hold a competence certificate and show it on request. When units are taken away for servicing, the firm must leave the same number of equivalent units in their place, so the building is never left without extinguishers.

Turkey's disaster authority AFAD makes the same points: keep extinguishers easy to reach, make sure everyone knows where they are, fix them firmly to the wall, have them serviced yearly by a qualified company and always refill them after use. Hanging a “half-used” extinguisher back on the wall is therefore not enough; a partly used unit also needs to go for refilling.

Between annual services, users can do a quick visual check. The US Fire Administration suggests checking that the extinguisher is easy to reach, that the pressure gauge reads in the correct range, and that the cylinder, hose and nozzle show no dents, rust or damage, and keeping the outside free of dust and grease.

Choosing for home, kitchen and car

  • General use: the USFA says multi-purpose (ABC-labelled) extinguishers suit most home fires, and recommends the largest unit the user can safely and comfortably handle.
  • Location: on the way out, near a door, visible and easy to reach; not behind the hob or in a cupboard.
  • Cooking oil: the Cambridge Fire Department, passing on NFPA advice, says that if a small grease fire starts in a pan you should smother it by sliding the lid over the pan, turn off the burner, not move the pan, and leave the lid on until the pan has cooled. Never pour water on a burning pan. Only extinguishers rated for this class are suitable for oil and fat fires, and only trained adults should use them; the USFA notes they are usually found in commercial kitchens. If a fire on the hob gets out of control, move to a safe place and call 112.
  • Who should not use one: the USFA says young children and older adults should not use extinguishers; adults in the household should know where it is and how to use it.
  • Car: if you carry one, keep it secured in a bracket rather than loose in the boot. In a vehicle fire, first get yourself and others safely away from the car and the road, then call 112.

Training and positioning

An extinguisher on the wall is only useful if people know how to use it. AFAD's sequence is short and memorable: pull the pin, aim at the base of the fire, squeeze, sweep. The USFA describes the same steps and advises using an extinguisher only when all of these are true: others have been alerted, the fire brigade has been called, you are physically able to use it, the fire is small and contained to a single object or surface, you are safe from toxic smoke and you have a clear escape route. If any one is missing, leave the building and call 112.

At work, training sticks when it is combined with drills. The regulation requires at least one firefighting and evacuation drill per year and hands-on training in using extinguishers for team members and other staff. Positioning should keep escape routes and emergency exits clear while keeping an extinguisher within reach of someone heading for the exit.

Night patrol checks

In offices, warehouses and residential sites, most extinguishers spend the night unobserved. A short check in security officers' patrol orders catches problems before morning:

  • Is the extinguisher in place, and not blocked by pallets, boxes or furniture?
  • Are the pin and tamper seal intact, and is the gauge in range?
  • Is there visible damage to the cylinder or hose?
  • Are escape routes and emergency exit doors clear?

Recording any defect in the shift log and passing it to facility management in the morning closes the gap between annual services.

Quick checklist

  • Does each extinguisher type match the fire class of its area?
  • Do numbers and placement meet the area and 25-metre rules?
  • Is the last annual inspection date on the label, and is the fourth-year refill in the calendar?
  • Have used units been refilled?
  • Do staff and family members know the use sequence?

Common mistakes

  • Hiding the extinguisher in a cupboard: precious seconds are lost searching for it.
  • Re-hanging a used unit: even a short discharge means it needs refilling.
  • Using water on a cooking-oil fire: the wrong agent can make things worse.
  • Delaying escape because there is an extinguisher: if the fire has grown, leave and call 112.

A professional security partner helps put extinguisher and escape-route checks into night patrol orders, log defects and report them regularly to facility management. Titan Savunma is an Ankara-based private security company holding a Ministry of Interior operating licence under Law 5188 and ISO 9001, 14001, 45001, 22301 and 28000 certificates; it works with international companies in English and Turkish and plans sites in different provinces with a single point of contact. See our page on manned guarding.

Sources and Further Reading

← Back to Security BulletinBack to Top
For Your Organisation

Let’s Discuss Your Security Needs

Tell us about your operations and expectations so we can define the appropriate service scope together.

Contact

Request a Security Proposal for Your Organisation

Tell us your facility type, location and general requirements. Together, we can define a service scope that suits your organisation.

Tell Us What You Need

Fields marked * are required.

What Happens Next

  1. Initial DiscussionWe respond within 15 minutes and clarify your requirements and facility details together.
  2. Service ScopeWe assess staffing needs and the working arrangements.
  3. ProposalWe prepare our proposal for the agreed service scope.

General Directorates

Ankara · Çankaya
İstanbul · Levent

Nine regional directorates · 81 provinces

Looking for a role? Visit our careers page