Data Centres

EN 50600-2-5 Explained: Data Centre Protection Classes

A plain guide to EN 50600-2-5: the four protection classes, nested zones and islands, organisational measures, certification and what it means for guarding.

Titan SavunmaOriginal Article: Updated: Approximately 9 min read
Two security staff watching monitors in a control room, one speaking on the phone.
In This Article

EN 50600-2-5 is the security part of the European data centre standard series. It does one main thing: it asks the designer to give every space and every supply path of a data centre a protection class, and then sets requirements and recommendations for each class. There are four protection classes, applied separately to different threats: unauthorised access, intrusion, fires starting inside the data centre spaces, and environmental events inside and outside them. A higher class means stronger protection, and the classes are nested so that the most sensitive rooms sit behind several boundaries.

For a facility manager or a security provider in Turkey, the useful question is what this means on the ground. The short answer: the class plan tells you where people must be verified, where they must be escorted, which alarms need a defined response and which boundaries the guarding team actually owns. This explainer walks through the structure of the standard, the class concept, how zones map to classes, the split between organisational and technical measures, the certification route and the consequences for a staffing plan.

Where part 2-5 sits in the EN 50600 series

The introduction of the standard, readable in the public preview of the 2020 enquiry draft that became EN 50600-2-5:2021, explains the architecture. EN 50600-1 sets general concepts and the classification system. The 2-x parts are design standards: building construction (2-1), power supply and distribution (2-2), environmental control (2-3), telecommunications cabling (2-4) and security systems (2-5). The 3-x parts deal with operation and management, and the 4-x parts with key performance indicators. The draft names its intended users as architects, building designers and builders, system and installation designers and security managers, and says the series does not deal with the selection of IT equipment or software.

The 2021 edition replaced the 2016 edition. The foreword of the draft lists the main changes: a technical update of all clauses in response to user feedback, a new clause on protection against intrusion into data centre spaces, and added references to the building construction part so that security and constructional requirements are read together. Its normative references show which product standards the requirements lean on: EN 50131 for intrusion and hold-up alarm systems, EN 50136 for alarm transmission, EN 50518 for monitoring and alarm receiving centres, EN 60839-11-1 for electronic access control and EN 62676 for video surveillance.

The protection class concept

The scope of part 2-5 covers protection against four groups of events: unauthorised access (addressed through both organisational and technological solutions), intrusion, fire events igniting within data centre spaces, and other events inside or outside those spaces that would affect the defined level of protection. Each group has its own set of classes and its own implementation clause for Protection Classes 1 to 4. The table of contents also shows one exception worth noting: the clause on environmental events outside the data centre spaces lists implementation for Protection Classes 1 to 3 only.

A published certificate appendix from TÜV Informationstechnik gives a plain-language summary of the certifier's criteria, which were applied against the 2016 edition of part 2-5: four protection classes are defined, a class is assigned to all areas and supply paths of the data centre, and with regard to unauthorised access at least three protection classes must be implemented. In practice, a site certified this way cannot be a single fenced box with one level of security inside; it has to show several nested levels of access protection.

The standard also defines a term that matters for every reception desk. An authorised person is someone who has been assessed and then given access credentials to specific areas within the data centre. The order is important: assessment first, credential second, and access limited to named areas.

Zones, islands and how spaces map to classes

The figure list in the preview describes the geometry. One figure places the protection classes within a four-layer physical protection model; others show "protection class islands" and the connections between them, and two examples apply the classes to premises with and without an external physical barrier. The unauthorised-access clause then works through the parts of a real site: premises with and without external barriers, roofs, access routes, parking, employees and visitors, pathways, and cabinets, racks and frames.

Two practical points follow. First, classes do not have to be a single onion; a site can contain several islands of a higher class, such as a meter room or a fuel area, each of which needs its own boundary and its own route back to a lower class. Second, the boundary between classes is where people and goods are checked. As an illustration only, since the class of each space is a design decision taken after the risk analysis the standard requires, an outline mapping might look like this:

  • Lowest class: site approach, parking and public-facing reception, where identity is first established.
  • Next class: general building areas, offices and corridors open to staff and registered visitors.
  • Higher class: technical support spaces such as electrical rooms, cooling plant and the loading bay that leads to them.
  • Highest class: data halls, network rooms and other spaces where a failure or tampering would directly affect the IT load.

The same thinking appears outside Europe. NIST's SP 800-116 Rev. 1 on credentials in facility access uses nested "Controlled, Limited, Exclusion" areas and recommends a minimum of one, two and three authentication factors respectively, noting that when areas are nested, authentication already performed at an outer boundary can count toward an inner one. It is not part of EN 50600, but it shows why nested classes and stronger verification at each step are a widely shared design logic.

Organisational versus technical measures

Part 2-5 deliberately covers both. Its closing clause on systems to prevent unauthorised access and intrusion lists the technology: security lighting, video surveillance systems, intruder and hold-up alarm systems, access control and alarm monitoring. But the scope says unauthorised access is addressed through organisational as well as technological solutions, and the clauses on employees and visitors show that procedures are expected, not optional.

Organisational measures that a guarding and reception team typically carries include:

  • verifying identity and authorisation before issuing a credential for a given class;
  • escorting visitors and contractors through boundaries they are not cleared to cross alone;
  • receiving and acting on alarms from the monitoring system according to a written response plan;
  • checking that doors at class boundaries close and are not propped open;
  • recording deliveries and equipment movements at the loading bay;
  • controlling keys for cabinets, racks and service doors.

Operational records belong in the management framework of EN 50600-3-1, the series' part on management and operational information. A class plan with no matching procedures and records will not survive an assessment, and in daily life it will not stop tailgating.

The certification route

EN 50600 itself is a standard, not a certificate. Conformity is assessed by third-party certification bodies against their own criteria catalogues. The TÜV certificate cited above is a good model of the output: it names the assessed security area, states the availability class, the protection classes and the energy-monitoring granularity achieved, lists the parts of EN 50600 used as evaluation requirements, and is valid for two years. When a provider or landlord in Turkey says a facility is "EN 50600 compliant", ask three questions: was it assessed by an independent body, which classes were achieved for which spaces, and is the certificate still valid?

A design assessment says nothing about whether the procedures are followed after handover. For that, operators usually rely on an ISO/IEC 27001 management system and its internal audits, and on records kept by the security team.

What the class plan means for a staffing plan

The standard does not set guard numbers and neither should anyone quoting it. What it does is define the work. Each class boundary that relies on a person, rather than a fully automated portal, needs cover during the hours it is used. Each alarm type that requires a response needs someone with a defined route and authority to respond. Each visitor flow needs a desk and an escort capacity. Staffing therefore depends on the shift pattern, the opening hours of each boundary, the number of active entry points, expected visitor and delivery volumes and legal working-time limits, and it is planned site by site.

In Turkey, people carrying out these tasks as security officers work under Law No. 5188. Article 7 of the Law sets their powers, including passing people through walk-through detectors and screening belongings with X-ray equipment at protected areas; anything beyond those powers should be designed into technology or into the client's own procedures, not assumed. Post orders should name the class of each boundary, the checks performed there and the record created. For the end of a contractor's access, see our article on ending contractor access after data centre maintenance.

Checklist: reading a design against EN 50600-2-5

  • Is there a written risk analysis behind the class assignments?
  • Does every space and every supply path have a class for each threat group?
  • Are at least three protection classes against unauthorised access in place, as certification criteria such as TÜV's expect?
  • Are class islands, such as fuel or electrical rooms, connected to the right lower class?
  • Are boundary checks, escorts and alarm responses written into post orders?
  • Does the alarm monitoring arrangement reflect the referenced alarm and monitoring standards?
  • Is there a current third-party certificate naming the classes achieved?

How Titan Savunma can help

Titan Savunma is an Ankara-based private security company licensed by the Ministry of Interior under Law No. 5188, holding ISO 9001, 14001, 45001, 22301 and 28000 certificates. We work in English and Turkish with international operators and tenants and plan services across provinces with a single point of contact, a written scope and regular reporting. Our manned guarding and data centre physical security pages describe how we translate a class plan into post orders; for wider infrastructure sites see critical infrastructure security.

Sources and Further Reading

← Back to Security BulletinBack to Top
For Your Organisation

Let’s Discuss Your Security Needs

Tell us about your operations and expectations so we can define the appropriate service scope together.

Contact

Request a Security Proposal for Your Organisation

Tell us your facility type, location and general requirements. Together, we can define a service scope that suits your organisation.

Tell Us What You Need

Fields marked * are required.

What Happens Next

  1. Initial DiscussionWe respond within 15 minutes and clarify your requirements and facility details together.
  2. Service ScopeWe assess staffing needs and the working arrangements.
  3. ProposalWe prepare our proposal for the agreed service scope.

General Directorates

Ankara · Çankaya
İstanbul · Levent

Nine regional directorates · 81 provinces

Looking for a role? Visit our careers page