Whether access-controlled doors open when the fire alarm sounds should never be left to chance. In Turkey, the Regulation on the Fire Protection of Buildings requires escape route doors to be openable by hand and not kept locked, and lists among the functions of the emergency control system that runs during a fire the opening of doors and turnstiles kept locked for security reasons. Technology releases the doors; trained guards manage the security gap that opens while the building is evacuated.
This article is general information, not legal advice. The solution for each door in your building should be decided with the fire safety designer and the competent fire authority.
Our encyclopedia covers access control systems and the basics of the escape route and emergency exit. This article sits where the two meet: lock types, the relevant provisions of the Turkish regulation, the fire alarm to access control interface, and the guard's role during an alarm.
Fail-safe and fail-secure
Electrically controlled locks fall into two groups depending on how they behave when power is lost:
- Fail-safe (unlocks without power): the lock needs power to stay locked. When power is cut or a release signal arrives, the door is free. The priority is that people can get out.
- Fail-secure (stays locked without power): the lock needs power to open. When power is cut, the door stays locked. The priority is protecting the space. If such a door is on an escape route, mechanical egress from the inside must be considered separately.
The choice depends on whether the door is on an escape route. A door on an escape route must not trap people during a power cut, a fire alarm or a system fault. A door that is not on an escape route, such as an archive or server room door, may justify a different approach for security reasons. This decision cannot be left to the security team alone; it is made together with the fire safety design and the architectural project.
What the Turkish regulation says about escape routes
The Regulation on the Fire Protection of Buildings (Council of Ministers Decision 2007/12937, Official Gazette of 19 December 2007, No. 26735) contains several clear provisions. We read the current consolidated text on mevzuat.gov.tr:
- Article 30(4): escape routes must be freely and unobstructedly accessible from every part of the building and kept maintained; locks, bolts and similar components that obstruct free escape may not be fitted to exits or doors. The article allows a narrow exception for certain special occupancies with permanently present staff and the means to evacuate occupants.
- Article 47(1): revolving doors and turnstiles may not be used as exit doors, so a lobby with turnstiles needs a separate escape door.
- Article 47(2): escape route doors must be openable by hand and not kept locked; in spaces with an occupant load above 50, exit doors must open in the direction of escape.
- Article 47(5): escape doors opening at ground level from a stair to a safe area, and, where more than 100 people are on a floor, doors of escape stairs, escape corridors and fire safety lobbies, must open in the direction of escape without using a door handle.
The fire alarm and access control interface
Article 82 lists the functions of the emergency control system that operates automatically in a fire. They include releasing electromagnetic holders that keep fire doors open, smoke control, emergency lighting and opening doors and turnstiles kept locked for security or similar reasons. The same article lists automatic notification of the fire to parties such as the fire brigade, police or gendarmerie and the building owner.
Its second paragraph is critical for integration: emergency control operations are carried out by control units within the fire alarm system, and control actions by other systems, such as building automation, must in no way prevent the emergency control actions made from the fire control panel. Access control software is one of those other systems. In practice, door release should depend on a command from the fire alarm system, not on the good behaviour of the access control software, and the access system must not delay that command.
In Europe there is also a dedicated standard for electrically controlled exit systems on escape routes. According to its published scope, EN 13637:2015 sets manufacturing, performance and test requirements for electrically controlled exit systems designed for use on escape routes, and describes each system as an initiating element that requests release, an electrical locking element that secures the door, and a controlling element that powers and controls the other two. Mechanical panic and emergency exit hardware falls under EN 1125 and EN 179. Whether to require conformity with these standards in a specification is a decision for the fire safety designer.
The security gap during an alarm, and the guard's role
When doors release, the building's security envelope is temporarily gone. That is unavoidable and right: life safety comes first. But if this period is not planned, two risks follow: nobody knows who left or entered among the evacuating crowd, and high-value or sensitive areas are left unwatched. Post orders and trained guards, not technology, close that gap:
- The control room sees the type and location of the alarm, follows the situation on camera and keeps contact with the fire brigade and building management.
- Floor and exit guards direct people to escape routes, point them to escape doors rather than turnstiles or revolving doors, and follow the flow to the assembly point.
- Guards at entry points politely stop people trying to enter during evacuation and only help fire and authorised emergency teams in.
- Sensitive areas (cash rooms, archives, server rooms) are observed from a safe distance and checked afterwards; no guard stays in the building to protect them.
- After the fire alarm is reset, each door is checked to confirm it has relocked, and doors left open or unusual access events go into the incident report.
Testing and exercises
The door to fire interface must work every day, not just on commissioning day. A sensible routine:
- Periodic function test: with the fire safety officer and maintenance contractor, a test command is sent from the fire panel and every door and turnstile on the escape route is checked and recorded as released.
- Power failure test: confirm that escape route doors can still be opened when power is cut.
- Test after software changes: repeat the interface test after every change to the access control or fire alarm software.
- Evacuation drill: rehearse the guards' roles at exits and entry points with real movement, and check that doors relock afterwards.
Add specific scenarios for people with disabilities, visitors and areas with few staff on night shift.
Common mistakes
- Treating turnstiles as the only exit. The regulation does not accept revolving doors or turnstiles as exit doors.
- Leaving the interface to the access control software alone. The command should come from the fire system and must not be blocked.
- Adding an extra lock to an escape door "for security". A lock or bolt that obstructs free escape is contrary to the regulation.
- Never testing the doors during drills. A door that opens on paper may not open in a real fire.
A professional security partner
Titan Savunma is an Ankara-based private security company operating under a Ministry of Interior licence under Law 5188, certified to ISO 9001, 14001, 45001, 22301 and 28000, and working with international companies in English and Turkish. We plan guarding together with your technology, writing into post orders who watches the released doors and where guards stand during evacuation. Start with our free security risk assessment or see our office and business centre security page.